TMF-U Series 3 Phase Input - 1 Phase Output 10 kVA - 20 kVA Online UPS


TMF-U Series of three phases in / single phase out with high frequency online double conversion UPS is a stable and reliable UPS system designed according to international power grid environment and network systems requirements. Its excellent quality and perfect usability provide safe network power supply with reliable protection and satisfy the users requirements of protecting overall equipment.


  • DSP Processor Technology
  • High Frequency Double Conversion Technology
  • Wide Input Voltage Range; 110- 300 Vac
  • Input PFC
  • Output Power Factor 0,9
  • Selectable Battery Voltage ; 192 / 240 Vdc.
  • Selectable End of Discharge Battery Voltage (EOD) from Panel
  • 3/1 Phase or 1/1 Phase Operating Options
  • Cold Start
  • Zero Transfer Time
  • Energy Saving with Eco Mode
  • Smart Battery Management
  • Generator Compatible Operation
  • Charges Batteries While UPS OFF
  • Automatic Controlled Fan Speed
  • Standard RS 232 Communication
  • RS 485/SNMP/AS400/USB Com. Ports (Optional)
  • Emergency Power Off (EPO) (Optional)
  • Manual ByPass (Optional)
  • N+1 Parallel Operation (Optional)
  • Adding Extra Batteries for More Backup (Optional)
  • Electromagnetic Compatibility
MODEL TMF-U-10 TMF-U-10L TMF-U-15L TMF-U-20L
Apparent Power (kVA) 10 10 15 20
Active Power (kW) 9 9 13,5 18
INPUT
Voltage 3/1; 360Vac/380Vac/400Vac/415Vac
1/1; 208Vac/220Vac/230Vac/240Vac
Adjustable from LCD Panel
Voltage Tolerance 3/1; %50 Load (190-520) ±5 Vac;  %100 Load (277-520) ±5 Vac
1/1; %50 Load (110–300) ±5 Vac; %100Load (160–300) ±5 Vac
Frequency 40-70Hz±%0,5 (Automatic Detect)
Power Factor 3/1:≥0,95; 1/1:≥0,99
BYPASS
Bypass Voltage Tolerance 160Vac - Nominal Output Voltage +32Vac
Frequency 50/60Hz ± 5Hz
OUTPUT
Voltage 208Vac/220Vac/230Vac/240Vac – Selectable from LCD Panel
Voltage Regulation ±%1
Frequency OnlineMode: Sync with Mains (50/60Hz) / Battery Mode: ± 0,2 Hz
Wave Form Pure Sine Wave
Crest Factor  3:1
Harmonic Distortion Lineer Load ≤%2; Non Lineer Load ≤%5
Transfer Time Online Mode - Battery Mode: 0 ms
Inverter - Bypass Mode: 0 ms
Overload Capacity 3 min. for %105-%125 Load
30 secs for %125-150 Load
100 ms for >%150 Load
EFFICIENCY
Online Mode ≥%93
Battery Mode ≥%92
Eco Mode ≥%98
BATTERY
Battery Voltage 192Vdc/240Vdc (Selectable with Jumper)
Battery Quantity/Capacity 16*12V-9Ah NA
Battery Charge Current (Standart) 1 A NA
Battery Charge Current (Long) NA 7 A
Battery Charge Time 8 hrs for %90 Capacity
ALARMS
Low Battery Audible Alarm / 4secs
Overload Audible Alarm – Twice / 1sec
UPS General Faiure Long Audible Alarm 
ENVIRONMENTAL
Operating Temperature 0˚C - 40˚C
Relative Humidity %20-%90 (Non Condensed)
Audible Noise ≤58 dBA (from 1m.) ≤60 dBA (from 1m.)
COMMUNICATION
Standard RS232 / Optional USB Windows 98/2000/2003/XP/Vista/7/8
Optional SNMP Power Management with SNMP / Web Browser (Optional)
STANDARDS
LVD&EMC EN62040-1:2008 (LVD); EN62040-2:2006 (EMC)
PHYSICAL
Dimensions (WxDxH) mm 262*580*732 262*580*628
Weight (kg) 74 30 39 40